Rockwell Disclaimer: The product is used surplus. Urgent Automation is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because Urgent Automation is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, Urgent Automation makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Urgent Automation also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. Urgent Automation also makes no representations as to your right to install any such firmware on the product. Urgent Automation will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Urgent Automation is NOT an authorized distributor for this manufacturer and therefore the manufacturer’s warranty does not apply.
Product comes with Urgent Automation's 1-year warranty.
The 2000 Amp rated RGH320032E from Eaton is an RG type Series G circuit breaker with an RG frame. It is well suited for reverse feed applications. The RGH320032E is an 80% rated circuit breaker. The interrupt capacity specifications for the RGH320032E include a 50 kiloamp interrupting capacity at 600 Volts AC, a 65 kiloamp interrupting capacity at 480 Volts AC, and a 125 kiloamp interrupting capacity at 240 Volts AC. The RGH320032E is a three-pole circuit breaker with imperial line/load terminals. The trip module on the RGH320032E is an electronic LSI trip (Digitrip 310 RMS). Since extremely high voltages and currents are present in electrical systems, the RGH320032E should only be installed or serviced when it is not energized. Failure to follow this recommendation can result in serious injury or even death.
For reverse feed applications, special attention is required to ensure that voltages are not present when the RGH320032E is being serviced. Solvents and cleaning agents used to service the circuit breaker should be suitable for this purpose (some commercial solvents are known to cause damage to circuit breaker components). Maintenance or installation activities should be carried out by trained and experienced technicians. The RGH320032E should be inspected periodically. During an inspection, any dirt, grease, and soot should be removed. The circuit breaker should be checked for cracks and discoloration. Breakers with severe discoloration or cracks should be replaced. The RGH320032E has dimensions of about 406 x 393 x 247 millimeters. The approximate weight of the RGH320032E is 102 pounds.
Part Number/Catalog No. | RGH320032E |
Product Type | Molded Case Circuit Breaker |
kAIC @ 480VAC | 65 |
Amps | 2000 |
Poles | 3 |
Trip Unit | 310+ Electronic LSI |
Terminations | Imperial Tapped Line/Load Conductor |
Max. Rated Current | 2500 A |
Main Conducting Paths | 8 kV |
Endurance | 3,000 Operating Cycles |
Max. Switching Frequency | 60 1/h |
Rated Making Capacity | 20 A |
Rated Operational Voltage | 125/250 V |
Power Consumption @ 24 Vac | 612 VA |
Max. Opening Time | 62 ms |
Part Number/Catalog No. | RGH320032E |
Product Type | Molded Case Circuit Breaker |
kAIC @ 480VAC | 65 |
Amps | 2000 |
Poles | 3 |
Trip Unit | 310+ Electronic LSI |
Terminations | Imperial Tapped Line/Load Conductor |
Max. Rated Current | 2500 A |
Main Conducting Paths | 8 kV |
Endurance | 3,000 Operating Cycles |
Max. Switching Frequency | 60 1/h |
Rated Making Capacity | 20 A |
Rated Operational Voltage | 125/250 V |
Power Consumption @ 24 Vac | 612 VA |
Max. Opening Time | 62 ms |