Rockwell Disclaimer: The product is used surplus. Urgent Automation is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because Urgent Automation is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, Urgent Automation makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Urgent Automation also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. Urgent Automation also makes no representations as to your right to install any such firmware on the product. Urgent Automation will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Urgent Automation is NOT an authorized distributor for this manufacturer and therefore the manufacturer’s warranty does not apply.
Product comes with Urgent Automation's 1-year warranty.
The JDB2100 is a type JDB series C molded case circuit breaker designed and manufactured by Eaton Corporation. The circuit breaker has a non-interchangeable trip unit which allows instantaneous and Long-time trip functions. The JDB2100 has load and line terminals and has standard interrupt capacity. The circuit breaker has a fixed thermal fixed magnetic trip mechanism to provide the required protection to a circuit. The JDB2100 has two poles and is rated to be used in circuits with a rated Amperage of 100 Amps and a voltage of 600 Volts AC. Additionally, the Cutler Hammer JDB2100 is specifically designed to protect circuits that are powered from a single-phase power source. The circuit breaker uses a J-frame type and accommodates a feed-thru connection.
The JDB2100 also accommodates an optional shunt trip, an optional undervoltage release, and an optional alarm switch. The circuit breaker, as with other Eaton molded case circuit breakers with non-interchangeable trip units, is suitable for reverse feed use. The JDB2100, by having a molded case, protects its internal components against moisture. The case also does not support the growth of fungus. Being a J-framed circuit breaker, the JDB2100 can be ordered in its constituent parts which are advantageous in case field installation is required. However, user assembled circuit breakers cannot be used for reverse feed use. Note that all J-framed circuit breakers from Eaton are HACR rated. As with other circuit breakers manufactured by Eaton, the JDB2100 goes through 2 calibration tests on each pole to ascertain its operating mechanism, accuracy, trip mechanism and continuity.
Part Number/Catalog No. | JDB2100 |
Product Type | Molded Case Circuit Breaker |
Series | C |
Frame | J |
Poles | 2 |
Amps | 100 |
Interrupting Capacity | 65 kA @ 240V |
Rating | 600 Vac |
Dimensions (W x H x D) | 4.13 x 10 x 4.06 in. |
Part Number/Catalog No. | JDB2100 |
Product Type | Molded Case Circuit Breaker |
Series | C |
Frame | J |
Poles | 2 |
Amps | 100 |
Interrupting Capacity | 65 kA @ 240V |
Rating | 600 Vac |
Dimensions (W x H x D) | 4.13 x 10 x 4.06 in. |